Technical calculation · General ventilation

Ventilation calculation.

Calculate the required ventilation airflow, an example fan arrangement and the fresh air louvre area from the room volume and air changes per hour.

Room dimensions

m
m
m
1/h

How many times per hour the air is replaced.

kW

Total of heat sources such as furnaces, machines and motors.

°C

Maximum by which the indoor air may be warmer than the outdoor air.

3D view

Air sweeps the space from end to end

Fresh air enters through the louvres, crosses the full length of the space and is exhausted by the fans. The building dimensions, number of fans and flow velocity come from your calculation.

Preparing the 3D view…

The illustration explains the preliminary calculation; it is not to scale. The view changes as you change the values.

Calculation method

How is ventilation airflow calculated?

In general ventilation, the airflow is found from how many times per hour the air in the space has to be replaced. In spaces with a high heat load, the airflow needed to remove the heat is calculated as well; the larger of the two values governs.

V = length × width × height
Q = V × nn: air changes per hour
Qheat (m³/h) ≈ 2,985 × P (kW) ÷ ΔT (°C)3,600 ÷ (ρ × cp) = 3,600 ÷ (1.2 × 1.005) ≈ 2,985
Alouvre = Q ÷ (3,600 × 2 m/s)

Worked example

A 40 × 20 × 8 m welding shop:

Volume: 40 × 20 × 8 = 6,400 m³

Airflow: 6,400 × 12 = 76,800 m³/h

Application: for example 6 fans × 12,800 m³/h and ≈ 10.7 m² of net louvre area for fresh air

Typical air change rates
Type of space1/h
Warehouse, storage4
General production area6
Machining, assembly workshop8
Welding and metalworking shop12
Textile, heat-loaded production15
Paint, solvent, chemical areas20
Foundry, hot process25

These are approximate values for general ventilation; they do not replace extraction at source.

Points to watch

Common mistakes in ventilation

  • Do not forget the fresh air inlet. As much air must enter as is extracted; if the louvres are too small the fans cannot deliver their airflow and doors become hard to open.
  • Extraction at source is required. In work such as welding and grinding, general ventilation alone does not remove fume and dust; extraction at source (a local filter) is needed.
  • Set up the airflow along the length of the space. Place fans and louvres opposite each other so that the air sweeps the space from end to end.
  • The values in the table are typical. Where a regulation or process requirement applies, that value governs.

Leave the calculation to our engineers.

Send us your airflow, dust type and plant layout; we will size the fan, filter and duct line together and prepare your quotation.